- You have no items in your cart.
- Home /
- StreamMaster II Electric Fire Monitor 1250 GPM (4800 LPM)
Overview
Specifications
Drawings
Installation / Service
Performance
Software/Multimedia
Features
- Compact industry-leading operating envelope (6", 152 mm)
- Lightweight Pyrolite construction
- Simple “plug and play” installation
- Integrated wireless compatibility, utilizing the optional 3600 hand held remote control
- Waterproof control system with locking connectors
- User programmable obstacle avoidance
- User programmable stow and deploy positions
- Superior range of motion
- Rotation range 355°
- Elevation range +120°, - 45°
- 12V or 24V operation
- Compatible with 3406 Electric Riser
- Now available with permanently attached handwheel overrides as an option (must specify)
- Patents #8,678,022, 9,233,265, 9,675,826, 102-122150, 4485, 2,876,669, 104620035B
Applications/Solutions
- Emergency Responder OEMs
- Fire OEMs
- Firefighting - Structural
StreamMaster II Electric Fire Monitor 1250 GPM (4800 LPM) Video
Specifications
Style | 3482 |
---|---|
Certification(ss) |
|
Warranty | |
Weight | 41.7 lbs. (18.9 kg) |
Material | Pyrolite |
Brand | StreamMaster |
Width | 11 5/8'' (295 mm) |
Height | 15'' (381 mm) |
Depth | 12 1/2'' (318 mm) |
Inlet | 3" 150 lb. flange (DN80 PN16 flange) |
Outlet | 2 1/2'' Male (65 mm) |
Flow (GPM) | 1250 |
Flow (LPM) | 4800 |
Volts | 12 V or 24 V |
SPECIFICATION FOR STYLE 3482 – 1250 GPM (4800 LPM)
The 1250 gpm (4800 lpm) rated monitor is to be an all-electric, single waterway monitor constructed of lightweight Pyrolite. The monitor shall have a 3”(75 mm), 150lb flanged inlet and 2-1/2” (65 mm) NH outlet. The monitor shall have cast-in turning vanes in each elbow. The monitor shall have fully enclosed motors and gears with manual overrides for both horizontal and vertical rotation and may be operated simultaneously. The monitor is not to exceed 15” (381 mm) high and 11-5/8” (295 mm) wide. The vertical travel shall be from 45° below to 120° above horizontal with adjustable stops at -15°, +45° and +90. The horizontal rotation shall be 355° with physical stops at ±45°, ±90°, ±135° and at ±157°. The monitor shall have absolute position feedback to provide programmable soft stops anywhere within the physical travel range. The control system shall also provide programmable oscillation and obstacle avoidance functions. These programmable features shall be capable of being copied and cloned for fast installment on other monitors using a USB stick. The electronic control system shall be attached to the inlet base of the monitor and be totally encapsulated to prevent moisture intrusion and use locking electrical connectors for all motor control outputs and control inputs. The control system shall have one environmentally sealed USB port to facilitate control system updates. The control system shall receive commands from J1939 CAN network control devices to control elevation, rotation, nozzle pattern, and electric valve open/close. The control system shall have a built in wireless transceiver to facilitate operation from wireless remote control devices.
SPECIFICATION FOR STYLE 3482 with Handwheel Overrides– 1250 GPM (4800 LPM)
The 1250 gpm (4800 lpm) rated monitor is to be an all-electric, single waterway monitor constructed of lightweight Pyrolite. The monitor shall have a 3”(75 mm), 150lb flanged inlet and 2-1/2” (65 mm) NH outlet. The monitor shall have cast-in turning vanes in each elbow. The monitor shall have fully enclosed motors and gears with manual handwheel overrides for both horizontal and vertical rotation and may be operated simultaneously. The monitor is not to exceed 15” (381 mm) high and 11-5/8” (295 mm) wide. The vertical travel shall be from 45° below to 120° above horizontal with adjustable stops at -15°, +45° and +90. The horizontal rotation shall be 355° with physical stops at ±45°, ±90°, ±135° and at ±157°. The monitor shall have absolute position feedback to provide programmable soft stops anywhere within the physical travel range. The control system shall also provide programmable oscillation and obstacle avoidance functions. These programmable features shall be capable of being copied and cloned for fast installment on other monitors using a USB stick. The electronic control system shall be attached to the inlet base of the monitor and be totally encapsulated to prevent moisture intrusion and use locking electrical connectors for all motor control outputs and control inputs. The control system shall have one environmentally sealed USB port to facilitate control system updates. The control system shall receive commands from J1939 CAN network control devices to control elevation, rotation, nozzle pattern, and electric valve open/close. The control system shall have a built in wireless transceiver to facilitate operation from wireless remote control devices.
Documents
Name | Sheet # | |
---|---|---|
3480 StreamMaster II Order Form |
Access Drawings for Engineers
Contact Us with Questions
Name | Instructions | Last Modified | Type |
---|---|---|---|
Style 3482 STP File - Horizontal Nozzle | 2016-02-25 20:18:27 | ||
Style 3482 STP File - Vertical Nozzle | 2016-02-25 20:20:13 | ||
Style 3482 STP File (4" Flange) | 2017-03-01 21:12:29 | ||
Style 3482 STP File (DN 80 flange) - Horizontal nozzle | 2017-07-05 23:22:02 | ||
Style 3482 STP File (DN 80 flange) - Vertical Nozzle | 2017-07-05 23:23:30 |
Installation and Service Documents
Contact Us with Questions
Performance Content
Contact Us with Questions
Name | Type |
---|---|
Style 3480 & 3482 EC Declaration of Conformity for Streammaster II |
Software Updates and Downloads
Contact Us with Questions
Type | Description | Instructions | Version | Updated | File |
---|---|---|---|---|---|
Download into Product with Akroview or USB Flash Drive where available. |
1.1 | 2017-11-29 16:44:53 | |||
60520029-30 Config File Rev. 5-1 Moccasin Bend Waste Water Treatment Plant |
Download into Product with Akroview or USB Flash Drive where available. |
5.1 | 2022-12-22 21:22:29 | ||
Download into Product with Akroview or USB Flash Drive where available. |
6.8 | 2022-12-22 21:20:17 | |||
P-Code for 60520003, 0004, 0011, 0012, 0013, 0014, 0019, 0020, 0023, 0024 only) |
Download into Product with Akroview or USB Flash Drive where available. |
6.5 | 2020-12-11 21:28:05 | ||
6052 P-Code File Rev. 6.0 (use on 60520021, 0022 only) only use on 60520021, 0022 |
Download into Product with Akroview or USB Flash Drive where available. |
6.0 | 2020-12-11 21:36:22 | ||
60520003, 0004 Config File Rev. 6.3 AUX button on wireless handheld mapped to Oscillate function (default firmware) |
Download into Product with Akroview or USB Flash Drive where available. |
6.3 | 2021-06-04 16:51:21 | ||
60520011-12 Config File Rev. 6.1 AUX button on wireless handheld mapped to Stow function |
Download into Product with Akroview or USB Flash Drive where available. |
6.1 | 2021-06-04 16:52:35 | ||
Download into Product with Akroview or USB Flash Drive where available. |
6.2 | 2021-06-04 16:56:15 | |||
60520013-14 Config File Rev. 6.1 AUX button on wireless handheld mapped to Discharge function |
Download into Product with Akroview or USB Flash Drive where available. |
6.1 | 2021-06-04 16:53:48 | ||
60520019-20 Config File Rev. 6.1 StreamMaster 2 Config File, AUX button mapped to Deploy |
Download into Product with Akroview or USB Flash Drive where available. |
6.1 | 2021-06-04 16:55:09 | ||
60520021-22 Config File Rev. 6.2 For use on 60520021, 0022 only |
Download into Product with Akroview or USB Flash Drive where available. |
6.2 | 2022-12-22 21:21:32 |
Product Updates and Media Files
Description | Type | Size | |
---|---|---|---|
StreamMaster II Electric Monitor Flyer | n/a | ||
Nozzle Monitor Compatibility Chart for Municipal Montiors | n/a | ||
StreamMaster II with Aerial Valve Manifold Video | n/a |
Related Products
1578 |
SaberMaster™ Electric Master Stream Nozzle... |
The SaberMaster nozzles are the only multi-purpose master stream nozzles in the fire service today. Find a distributor n...
|
6039 |
CAN I/O Module... |
The 6039 CAN I/O modules are primarily for use with Akron Brass "on monitor" controls that have limited I/O capability. ...
|
3481 |
StreamMaster II Manual Fire Monitor System 2000 GPM (7600 LP... |
The Style 3481 StreamMaster™ II manual water cannon with its multiple patent pending design, provides efficient... |
3480 |
StreamMaster™ II Electric Fire Monitor System | 2000 GPM (... |
The StreamMaster™ II mid-range, electric fire monitor’s patent-pending design provides efficient flows in a compact ...
|
5177 |
Akromatic 1250 Electric Master Stream Nozzle... |
The Akromatic 1250 electric master stream nozzle is designed for flows from 350 to 1250 gpm (1326-4800 lpm) that have an...
|
4040 |
Akrochem Master Stream Nozzle Electric Pattern Actuation... |
Akrochem nozzles provide both dry chemical application and foam/water application. This flexible nozzle combines the ... |
3485 |
2.5" Mini Stream Shaper... |
Designed with built-in offset fins to maximize reach....
|
2498 |
Triple Stacked Tips... |
Stacked Tips
- Chrome plated aluminum - Standard orifices 1-1/2" x 1-3/4" x 2 - Optional orifices 1... |
2499 |
Quad Stacked Deluge Tips... |
These smooth bore nozzle quad stacked deluge tips help you increase tip size quickly and effectively.
|
3406 |
Electric Riser for DeckMaster and StreamMaster... |
The electric riser provides an additional 12 inches (305 mm) of extension and is the perfect complement to the already s...
|
6041 |
CAN Toggle Switch Box... |
The 6041 CAN Toggle Switch Box provides monitor positioning control over the J1939 CAN network. This product is part of ...
|
6035 |
CAN Proportional Joystick ... |
The 6035 CAN Proportional Joystick provides precise monitor positioning control over the J1939 CAN network. This prod... |
3600 |
Handheld Wireless Remote Control - DISCONTINUED... |
Discontinued effective January 2024 |
6041 |
CAN Tethered Remote... |
The 6041 CAN Tethered Remote provides monitor positioning control over the J1939 CAN network. This product is part of th...
|
6036 |
CAN Position Indicator... |
The 6036 CAN Position Indicator provides a graphical representation of monitor position for remote operators that are un...
|
6046 |
Diagnostic Interface with Akroview ... |
The 6046 Diagnostic Interface Kit provides a method of connecting a PC to the Akron Brass CAN network This product is pa...
|
6051 |
CAN to CAN Gateway/Repeater... |
The 6051 CAN Gateway/Repeater provides communication between dissimilar network protocols such as J1939 and CANopen. It ...
|